Grade & Surface finish guidelines for tubes.
Pharmaceutical tubing require stringent specifications to meet the high standards of cleanliness, corrosion resistance, and smooth surface finish necessary for these critical applications. Below are the detailed guidelines for grades and surface finishes for pharmaceutical tubes:

- SS 316 L is used when ozone is used in disinfection system.
- 304 L is resistance to crevice and pitting type corrosion when chloride concentration is up to 500 mg/l with free chlorine concentration up to 5 mg/ltr at room temp. if temp > 50 degC then use SS 316 L
Details High quality Stainless steel Sanitary Tubes
3-A Sanitary Standards Tubes Dimensions & Specifications

BS-4825 Sanitary Standards Tubes Dimensions & Specifications

ISO – SMC Sanitary Standards Tubes Dimensions & Specifications

ASME-BPE Sanitary Standards Tubes Specifications

Surface finish as per ASME – BPE

Surface Finish Comparison Grit & Ra

Also Read,